Model Implementation Conformance Statement
for the IEC61850 interface in Shark 200 ICD
19-Mar-2013, 1.0

Table of Contents

Introduction

This model implementation conformance statement is applicable for ElectroIndustries, S200(Electro Industries Shark 200) , with firmware 1.00 .

This MICS document specifies the modelling extensions compared to IEC 61850 edition 1. For the exact details on the standardized model please compare the ICD substation configuration file: [filename.icd], version [version].

Clause 2 contains the list of implemented logical nodes.
Clause 3 describes the new and extended logical nodes.
Clause 4 describes the new and extended common data classes (if any).
Clause 5 describes the new and extended enum types.
Clause 6 describes any other extensions.

IEC 61850 Data Model Definitions


IEDs within Shark 200 ICD

IED Name Type Manufacturer Config Version
SHARK200IEC S200 ElectroIndustries 1.00

Logical Device list

Logical Device Instances within IED SHARK200IEC (Electro Industries Shark 200); AccessPoint: S1(); Server: ():

Instance Description Default Namespace
Meas Measurement Unit IEC 61850-7-4:2003

Proprietary Logical Nodes

Proprietary Logical Nodes within IED SHARK200IEC:

Logical Device SHARK200IECMeas (Instance Meas of SHARK200IEC): Measurement Unit

Name LN Type Description lnNs

Proprietary Data Objects

Proprietary Data Objects within IED SHARK200IEC:

Logical Device SHARK200IECMeas (Instance Meas of SHARK200IEC): Measurement Unit

LDevice LN DO dataNs cdcNs

Subscribed GOOSEes for IED SHARK200IEC

No GOOSE subscriptions in IEDSHARK200IEC

Published GOOSEes for IED SHARK200IEC

No GOOSE publications in IEDSHARK200IEC

Logical Node list


Logical Nodes within Logical Device SHARK200IECMeas (Instance Meas of SHARK200IEC)

L: System Logical Nodes
Name LN Type Description
LLN0 SHK2_LLN0 Logical Device Description
LPHD1 SHK2_LPHD Physical Device Description

M: Metering and Measurement
Name LN Type Description
nsMMXU1 SHK2_MMXU Basic Measurements
nsMHAI1 SHK2_MHAI Harmonic Measurements
eneMMTR1 SHK2_MMTR Energy Metering

T: Instrument Transformer (Transducers)
Name LN Type Description
setTCTR1 SHK2_TCTR CT Ratio Phase A
setTCTR2 SHK2_TCTR CT Ratio Phase B
setTCTR3 SHK2_TCTR CT Ratio Phase C
setTCTR4 SHK2_TCTR CT Ratio Neutral
setTVTR1 SHK2_TVTR VT Ratio Phase A
setTVTR2 SHK2_TVTR VT Ratio Phase B
setTVTR3 SHK2_TVTR VT Ratio Phase C


DataSet List

DataSets within Logical Device Instance Meas of AccessPoint S1 of IED SHARK200IEC

(Note: all datasets within this IED are identically configured)
2 pre-defined datasets exist within this Logical Device/AccessPoint.
Datasets are read-only
Dataset directory services are supported
Datasets cannot be created at runtime.
Logical Node Name Description
Meas/LLN0 Basics
Meas/LLN0.Mod [ST]
Meas/LLN0.Beh [ST]
Meas/LLN0.Health [ST]
Meas/nsMMXU1.PhV.phsA.instCVal [MX]
Meas/nsMMXU1.PhV.phsB.instCVal [MX]
Meas/nsMMXU1.PhV.phsC.instCVal [MX]
Meas/nsMMXU1.A.phsA.instCVal [MX]
Meas/nsMMXU1.A.phsB.instCVal [MX]
Meas/nsMMXU1.A.phsC.instCVal [MX]
Meas/nsMMXU1.A.neut.instCVal [MX]
Meas/nsMMXU1.PPV.phsAB.instCVal [MX]
Meas/nsMMXU1.PPV.phsBC.instCVal [MX]
Meas/nsMMXU1.PPV.phsCA.instCVal [MX]
Meas/nsMMXU1.TotVA.instMag [MX]
Meas/nsMMXU1.TotVAr.instMag [MX]
Meas/nsMMXU1.TotW.instMag [MX]
Meas/nsMMXU1.Hz.instMag [MX]
Meas/nsMHAI1.ThdPhV.phsA.q [MX]
Meas/LLN0 JustVoltages
Meas/LLN0.Mod [ST]
Meas/LLN0.Beh [ST]
Meas/LLN0.Health [ST]
Meas/nsMMXU1.PhV.phsA.instCVal [MX]
Meas/nsMMXU1.PhV.phsB.instCVal [MX]
Meas/nsMMXU1.PhV.phsC.instCVal [MX]
Meas/nsMMXU1.PPV.phsAB.instCVal [MX]
Meas/nsMMXU1.PPV.phsBC.instCVal [MX]
Meas/nsMMXU1.PPV.phsCA.instCVal [MX]
Meas/nsMHAI1.ThdPhV.phsA [MX]

Logical Node Definitions based upon IED declarations

Logical Nodes within: SHARK200IEC, LD inst=Meas

Logical node SHARK200IECMeas/LLN0: type= SHK2_LLN0, base class= LLN0: Logical Device Description


DATA Type M/O Description Transient Access Control
Mod SHK2_INC_Mod M Mode
Mod.stVal: (Template) (RO)on
Mod.ctlModel: (Template) (RO)status-only
Mod.d: (Template) (RO)Operating Mode
Beh SHK2_INS_Beh M Behaviour
Beh.stVal: (Template) (RO)on
Beh.d: (Template) (RO)Operating Mode Behavior
Health SHK2_INS_Health M Health
Health.stVal: (Template) (RO)Ok
Health.d: (Template) (RO)1=Ok,2=Warning,3=Alarm
NamPlt SHK2_LPL_LLN0 M Name plate
NamPlt.vendor: (Template) (RO)Electro Industries
NamPlt.swRev: (Template) (RO)
NamPlt.configRev: (Template) (Spec)1.0
NamPlt.d: (Template) (RO)Logical Device Nameplate
NamPlt.ldNs: (Template) (RO)IEC 61850-7-4:2003

Logical node SHARK200IECMeas/LPHD1: type= SHK2_LPHD, base class= LPHD: Physical Device Description


DATA Type M/O Description Transient Access Control
PhyNam SHK2_DPL O Physical device name plate
PhyHealth SHK2_INS_Health O Physical device health
PhyHealth.stVal: (Template) (RO)Ok
PhyHealth.d: (Template) (RO)1=Ok,2=Warning,3=Alarm
Proxy SPS M Indicates if this LN is a proxy
Proxy.stVal: (Instance) (Set)false
Proxy.d: (Instance) (RO)True if this LD is a proxy for an external device

Logical node SHARK200IECMeas/nsMMXU1: type= SHK2_MMXU, base class= MMXU: Basic Measurements


DATA Type M/O Description Transient Access Control
Mod SHK2_INC_Mod M Mode
Mod.stVal: (Template) (RO)on
Mod.ctlModel: (Template) (RO)status-only
Mod.d: (Template) (RO)Operating Mode
Beh SHK2_INS_Beh M Behaviour
Beh.stVal: (Template) (RO)on
Beh.d: (Template) (RO)Operating Mode Behavior
Health SHK2_INS_Health M Health
Health.stVal: (Template) (RO)Ok
Health.d: (Template) (RO)1=Ok,2=Warning,3=Alarm
NamPlt SHK2_LPL_STD M Name plate
NamPlt.vendor: (Template) (RO)Electro Industries
NamPlt.swRev: (Template) (RO)
NamPlt.d: (Template) (RO)Logical Node Nameplate
PhV WYE_ABC_mag_noDC O Phase to ground voltages (VL1ER, …)
PhV.d: (Instance) (RO)instantaneous normal speed Phase-to-Neutral(ground) voltage
A WYE_ABCN_mag_noDC O Phase currents (IL1, IL2, IL3)
A.d: (Instance) (RO)instantaneous normal speed Per-Phase Amperes
PPV DEL_ABC_mag_noDC O Phase to phase voltages (VL1VL2, …)
PPV.d: (Instance) (RO)instantaneous normal speed Phase-to-Phase voltage
VA WYE_ABC_mag_noDC O Phase apparent power (S)
VA.d: (Instance) (RO)instantaneous normal speed Per-Phase VAs
TotVA MV O Total Apparent Power (Total S)
TotVA.db: (Instance) (Spec)100000
TotVA.d: (Instance) (RO)instantaneous normal speed Total VAs
VAr WYE_ABC_mag_noDC O Phase reactive power (Q)
VAr.d: (Instance) (RO)instantaneous normal speed Per-Phase VArs
TotVAr MV O Total Reactive Power (Total Q)
TotVAr.db: (Instance) (Spec)100000
TotVAr.d: (Instance) (RO)instantaneous normal speed Total VArs
W WYE_ABC_mag_noDC O Phase active power (P)
W.d: (Instance) (RO)instantaneous normal speed Per-Phase watts
TotW MV O Total Active Power (Total P)
TotW.db: (Instance) (Spec)75000
TotW.d: (Instance) (RO)instantaneous normal speed Total Watts
Hz MV O Frequency
Hz.db: (Instance) (Spec)0
Hz.d: (Instance) (RO)instantaneous normal speed Frequency
PF WYE_ABC_mag_noDC O Phase power factor
PF.d: (Instance) (RO)instantaneous normal speed Per-Phase Power Factor
TotPF MV O Average Power factor (Total PF)
TotPF.db: (Instance) (Spec)100000
TotPF.d: (Instance) (RO)instantaneous normal speed Total Power Factor

Logical node SHARK200IECMeas/nsMHAI1: type= SHK2_MHAI, base class= MHAI: Harmonic Measurements


DATA Type M/O Description Transient Access Control
Mod SHK2_INC_Mod M Mode
Mod.stVal: (Template) (RO)on
Mod.ctlModel: (Template) (RO)status-only
Mod.d: (Template) (RO)Operating Mode
Beh SHK2_INS_Beh M Behaviour
Beh.stVal: (Template) (RO)on
Beh.d: (Template) (RO)Operating Mode Behavior
Health SHK2_INS_Health M Health
Health.stVal: (Template) (RO)Ok
Health.d: (Template) (RO)1=Ok,2=Warning,3=Alarm
NamPlt SHK2_LPL_STD M Name plate
NamPlt.vendor: (Template) (RO)Electro Industries
NamPlt.swRev: (Template) (RO)
NamPlt.d: (Template) (RO)Logical Node Nameplate
ThdPhV WYE_ABC_mag_noDC O Voltage Total Harmonic or Interharmonic Distortion (different methods) for phase to ground

Logical node SHARK200IECMeas/eneMMTR1: type= SHK2_MMTR, base class= MMTR: Energy Metering


DATA Type M/O Description Transient Access Control
Mod SHK2_INC_Mod M Mode
Mod.stVal: (Template) (RO)on
Mod.ctlModel: (Template) (RO)status-only
Mod.d: (Template) (RO)Operating Mode
Beh SHK2_INS_Beh M Behaviour
Beh.stVal: (Template) (RO)on
Beh.d: (Template) (RO)Operating Mode Behavior
Health SHK2_INS_Health M Health
Health.stVal: (Template) (RO)Ok
Health.d: (Template) (RO)1=Ok,2=Warning,3=Alarm
NamPlt SHK2_LPL_STD M Name plate
NamPlt.vendor: (Template) (RO)Electro Industries
NamPlt.swRev: (Template) (RO)
NamPlt.d: (Template) (RO)Logical Node Nameplate
DmdWh BCR O Real energy demand (default demand direction: energy flow from busbar away)
DmdWh.d: (Instance) (RO)Generated Watt-hours
SupWh BCR O Real energy supply (default supply direction: energy flow towards busbar)
SupWh.d: (Instance) (RO)Consumed Watt-hours
TotVAh BCR O Net apparent energy since last reset
TotVAh.d: (Instance) (RO)Total VA-hours
DmdVArh BCR O Reactive energy demand (default demand direction: energy flow from busbar away)
DmdVArh.d: (Instance) (RO)Generated VAr-hours
SupVArh BCR O Reactive energy supply (default supply direction: energy flow towards busbar)
SupVArh.d: (Instance) (RO)Consumed VAr-hours

Logical node SHARK200IECMeas/setTCTR1: type= SHK2_TCTR, base class= TCTR: CT Ratio Phase A


DATA Type M/O Description Transient Access Control
Mod SHK2_INC_Mod M Mode
Mod.stVal: (Template) (RO)on
Mod.ctlModel: (Template) (RO)status-only
Mod.d: (Template) (RO)Operating Mode
Beh SHK2_INS_Beh M Behaviour
Beh.stVal: (Template) (RO)on
Beh.d: (Template) (RO)Operating Mode Behavior
Health SHK2_INS_Health M Health
Health.stVal: (Template) (RO)Ok
Health.d: (Template) (RO)1=Ok,2=Warning,3=Alarm
NamPlt SHK2_LPL_STD M Name plate
NamPlt.vendor: (Template) (RO)Electro Industries
NamPlt.swRev: (Template) (RO)
NamPlt.d: (Template) (RO)Logical Node Nameplate
Rat ASG_Rat O Winding ratio of an external current transformer (transducer) if applicable
Rat.d: (Instance) (RO)CT Ratio Phase A

Logical node SHARK200IECMeas/setTCTR2: type= SHK2_TCTR, base class= TCTR: CT Ratio Phase B


DATA Type M/O Description Transient Access Control
Mod SHK2_INC_Mod M Mode
Mod.stVal: (Template) (RO)on
Mod.ctlModel: (Template) (RO)status-only
Mod.d: (Template) (RO)Operating Mode
Beh SHK2_INS_Beh M Behaviour
Beh.stVal: (Template) (RO)on
Beh.d: (Template) (RO)Operating Mode Behavior
Health SHK2_INS_Health M Health
Health.stVal: (Template) (RO)Ok
Health.d: (Template) (RO)1=Ok,2=Warning,3=Alarm
NamPlt SHK2_LPL_STD M Name plate
NamPlt.vendor: (Template) (RO)Electro Industries
NamPlt.swRev: (Template) (RO)
NamPlt.d: (Template) (RO)Logical Node Nameplate
Rat ASG_Rat O Winding ratio of an external current transformer (transducer) if applicable
Rat.d: (Instance) (RO)CT Ratio Phase B

Logical node SHARK200IECMeas/setTCTR3: type= SHK2_TCTR, base class= TCTR: CT Ratio Phase C


DATA Type M/O Description Transient Access Control
Mod SHK2_INC_Mod M Mode
Mod.stVal: (Template) (RO)on
Mod.ctlModel: (Template) (RO)status-only
Mod.d: (Template) (RO)Operating Mode
Beh SHK2_INS_Beh M Behaviour
Beh.stVal: (Template) (RO)on
Beh.d: (Template) (RO)Operating Mode Behavior
Health SHK2_INS_Health M Health
Health.stVal: (Template) (RO)Ok
Health.d: (Template) (RO)1=Ok,2=Warning,3=Alarm
NamPlt SHK2_LPL_STD M Name plate
NamPlt.vendor: (Template) (RO)Electro Industries
NamPlt.swRev: (Template) (RO)
NamPlt.d: (Template) (RO)Logical Node Nameplate
Rat ASG_Rat O Winding ratio of an external current transformer (transducer) if applicable
Rat.d: (Instance) (RO)CT Ratio Phase C

Logical node SHARK200IECMeas/setTCTR4: type= SHK2_TCTR, base class= TCTR: CT Ratio Neutral


DATA Type M/O Description Transient Access Control
Mod SHK2_INC_Mod M Mode
Mod.stVal: (Template) (RO)on
Mod.ctlModel: (Template) (RO)status-only
Mod.d: (Template) (RO)Operating Mode
Beh SHK2_INS_Beh M Behaviour
Beh.stVal: (Template) (RO)on
Beh.d: (Template) (RO)Operating Mode Behavior
Health SHK2_INS_Health M Health
Health.stVal: (Template) (RO)Ok
Health.d: (Template) (RO)1=Ok,2=Warning,3=Alarm
NamPlt SHK2_LPL_STD M Name plate
NamPlt.vendor: (Template) (RO)Electro Industries
NamPlt.swRev: (Template) (RO)
NamPlt.d: (Template) (RO)Logical Node Nameplate
Rat ASG_Rat O Winding ratio of an external current transformer (transducer) if applicable
Rat.d: (Instance) (RO)CT Ratio neutral

Logical node SHARK200IECMeas/setTVTR1: type= SHK2_TVTR, base class= TVTR: VT Ratio Phase A


DATA Type M/O Description Transient Access Control
Mod SHK2_INC_Mod M Mode
Mod.stVal: (Template) (RO)on
Mod.ctlModel: (Template) (RO)status-only
Mod.d: (Template) (RO)Operating Mode
Beh SHK2_INS_Beh M Behaviour
Beh.stVal: (Template) (RO)on
Beh.d: (Template) (RO)Operating Mode Behavior
Health SHK2_INS_Health M Health
Health.stVal: (Template) (RO)Ok
Health.d: (Template) (RO)1=Ok,2=Warning,3=Alarm
NamPlt SHK2_LPL_STD M Name plate
NamPlt.vendor: (Template) (RO)Electro Industries
NamPlt.swRev: (Template) (RO)
NamPlt.d: (Template) (RO)Logical Node Nameplate
Rat ASG_Rat O Winding ratio of external voltage transformer (transducer) if applicable
Rat.d: (Instance) (RO)VT Ratio Phase A

Logical node SHARK200IECMeas/setTVTR2: type= SHK2_TVTR, base class= TVTR: VT Ratio Phase B


DATA Type M/O Description Transient Access Control
Mod SHK2_INC_Mod M Mode
Mod.stVal: (Template) (RO)on
Mod.ctlModel: (Template) (RO)status-only
Mod.d: (Template) (RO)Operating Mode
Beh SHK2_INS_Beh M Behaviour
Beh.stVal: (Template) (RO)on
Beh.d: (Template) (RO)Operating Mode Behavior
Health SHK2_INS_Health M Health
Health.stVal: (Template) (RO)Ok
Health.d: (Template) (RO)1=Ok,2=Warning,3=Alarm
NamPlt SHK2_LPL_STD M Name plate
NamPlt.vendor: (Template) (RO)Electro Industries
NamPlt.swRev: (Template) (RO)
NamPlt.d: (Template) (RO)Logical Node Nameplate
Rat ASG_Rat O Winding ratio of external voltage transformer (transducer) if applicable
Rat.d: (Instance) (RO)VT Ratio Phase B

Logical node SHARK200IECMeas/setTVTR3: type= SHK2_TVTR, base class= TVTR: VT Ratio Phase C


DATA Type M/O Description Transient Access Control
Mod SHK2_INC_Mod M Mode
Mod.stVal: (Template) (RO)on
Mod.ctlModel: (Template) (RO)status-only
Mod.d: (Template) (RO)Operating Mode
Beh SHK2_INS_Beh M Behaviour
Beh.stVal: (Template) (RO)on
Beh.d: (Template) (RO)Operating Mode Behavior
Health SHK2_INS_Health M Health
Health.stVal: (Template) (RO)Ok
Health.d: (Template) (RO)1=Ok,2=Warning,3=Alarm
NamPlt SHK2_LPL_STD M Name plate
NamPlt.vendor: (Template) (RO)Electro Industries
NamPlt.swRev: (Template) (RO)
NamPlt.d: (Template) (RO)Logical Node Nameplate
Rat ASG_Rat O Winding ratio of external voltage transformer (transducer) if applicable
Rat.d: (Instance) (RO)VT Ratio Phase C

Common Data Class Definitions

Common DATA class SPS of variant SPS:

Attribute Type FC Description TrgOp R/W(value)
Status
stVal BOOLEAN ST TRUE | FALSE dchg
q Quality ST qchg
t Timestamp ST
Configuration, Description
d VisString255 DC Text

Common DATA class INS of variant SHK2_INS_Beh:

Attribute Type FC Description TrgOp R/W(value)
Status
stVal Enum Beh ST dchg RO(on)
q Quality ST qchg
t Timestamp ST
Configuration, Description
d VisString255 DC Text RO(Operating Mode Behavior)

Common DATA class INS of variant SHK2_INS_Health:

Attribute Type FC Description TrgOp R/W(value)
Status
stVal Enum Health ST dchg RO(Ok)
q Quality ST qchg
t Timestamp ST
Configuration, Description
d VisString255 DC Text RO(1=Ok,2=Warning,3=Alarm)

Common DATA class BCR of variant BCR:

Attribute Type FC Description TrgOp R/W(value)
Status
actVal INT64 ST dchg
q Quality ST qchg
t Timestamp ST
Configuration, Description
pulsQty FLOAT32 CF RO(1)
d VisString255 DC

Common DATA class MV of variant MV:

Attribute Type FC Description TrgOp R/W(value)
Measurand
instMag AnalogueValue MX
mag AnalogueValue MX dchg
q Quality MX qchg
t Timestamp MX
Configuration, Description
db INT32U CF
rangeC RangeConfig CF
d VisString255 DC Text

Common DATA class CMV of variant CMV_mag:

Attribute Type FC Description TrgOp R/W(value)
Measurand
instCVal Vector_mag MX
cVal Vector_mag MX dchg
q Quality MX qchg
t Timestamp MX
Configuration, Description
db INT32U CF
rangeC RangeConfig CF
d VisString255 DC Text

Common DATA class CMV of variant CMV_mag_noDC:

Attribute Type FC Description TrgOp R/W(value)
Measurand
instCVal Vector_mag MX
cVal Vector_mag MX dchg
q Quality MX qchg
t Timestamp MX
Configuration, Description
db INT32U CF
rangeC RangeConfig CF

Common DATA class WYE of variant WYE_ABC_mag:

Attribute Type FC Description TrgOp R/W(value)
phsA CMV_mag
phsB CMV_mag
phsC CMV_mag
Configuration, Description
d VisString255 DC Text

Common DATA class WYE of variant WYE_ABC_mag_noDC:

Attribute Type FC Description TrgOp R/W(value)
phsA CMV_mag_noDC
phsB CMV_mag_noDC
phsC CMV_mag_noDC
Configuration, Description
d VisString255 DC Text

Common DATA class WYE of variant WYE_ABCN_mag:

Attribute Type FC Description TrgOp R/W(value)
phsA CMV_mag
phsB CMV_mag
phsC CMV_mag
neut CMV_mag
Configuration, Description
d VisString255 DC Text

Common DATA class WYE of variant WYE_ABCN_mag_noDC:

Attribute Type FC Description TrgOp R/W(value)
phsA CMV_mag_noDC
phsB CMV_mag_noDC
phsC CMV_mag_noDC
neut CMV_mag_noDC
Configuration, Description
d VisString255 DC Text

Common DATA class DEL of variant DEL_ABC_mag:

Attribute Type FC Description TrgOp R/W(value)
phsAB CMV_mag
phsBC CMV_mag
phsCA CMV_mag
Configuration, Description
d VisString255 DC Text

Common DATA class DEL of variant DEL_ABC_mag_noDC:

Attribute Type FC Description TrgOp R/W(value)
phsAB CMV_mag_noDC
phsBC CMV_mag_noDC
phsCA CMV_mag_noDC
Configuration, Description
d VisString255 DC Text

Common DATA class DEL of variant DEL_ABCN_mag:

Attribute Type FC Description TrgOp R/W(value)
phsAB CMV_mag
phsBC CMV_mag
phsCA CMV_mag
Configuration, Description
d VisString255 DC Text

Common DATA class INC of variant SHK2_INC_Mod:

Attribute Type FC Description TrgOp R/W(value)
Status
stVal Enum Beh ST dchg RO(on)
q Quality ST qchg
t Timestamp ST
Configuration, Description
ctlModel Enum CtlModels CF RO(status-only)
d VisString255 DC Text RO(Operating Mode)

Common DATA class ASG of variant ASG_Rat:

Attribute Type FC Description TrgOp R/W(value)
Settings
setMag AnalogueValue SP
Configuration, Description
d VisString255 DC Text

Common DATA class DPL of variant SHK2_DPL:

Attribute Type FC Description TrgOp R/W(value)
Configuration, Description
vendor VisString255 DC RO(Electro Industries)
swRev VisString255 DC RO
serNum VisString255 DC RO
model VisString255 DC RO

Common DATA class LPL of variant SHK2_LPL_LLN0:

Attribute Type FC Description TrgOp R/W(value)
Configuration, Description
vendor VisString255 DC RO(Electro Industries)
swRev VisString255 DC RO
configRev VisString255 DC Spec(1.0)
d VisString255 DC RO(Logical Device Nameplate)
Extension
ldNs VisString255 EX shall be included in LLN0 only; RO(IEC 61850-7-4:2003)

Common DATA class LPL of variant SHK2_LPL_STD:

Attribute Type FC Description TrgOp R/W(value)
Configuration, Description
vendor VisString255 DC RO(Electro Industries)
swRev VisString255 DC RO
d VisString255 DC RO(Logical Node Nameplate)

Common DATA class LPL of variant SHK2_LPL_FLK:

Attribute Type FC Description TrgOp R/W(value)
Configuration, Description
vendor VisString255 DC RO(Electro Industries)
swRev VisString255 DC RO
d VisString255 DC RO(Logical Node Nameplate)
Extension
lnNs VisString255 EX RO(IEC 61850-7-4:2010)

Data Attribute Definitions

Attribute structure AnalogueValue:

Attribute Type Description R/W
f FLOAT32 The value of f shall be the FLOAT representation of the measured value. f shall represent the technological value in SI units.

Attribute structure AnalogueValue_RCconst:

Attribute Type Description R/W
f FLOAT32 RO(0.0)

Attribute structure AnalogueValue_RCvar:

Attribute Type Description R/W
f FLOAT32 The value of f shall be the FLOAT representation of the measured value. f shall represent the technological value in SI units. Spec(0.0)

Attribute structure ScaledValueConfig:

Attribute Type Description R/W
scaleFactor FLOAT32 Scaling factor
offset FLOAT32 Offset

Attribute structure RangeConfig:

Attribute Type Description R/W
hhLim AnalogueValue_RCconst Not Used
hLim AnalogueValue_RCconst Not Used
lLim AnalogueValue_RCconst Not Used
llLim AnalogueValue_RCconst Not Used
min AnalogueValue_RCvar Minimum process measurement used for %deadband. Spec
max AnalogueValue_RCvar Maximum process measurement used for %deadband. Spec

Attribute structure Vector_mag:

Attribute Type Description R/W
mag AnalogueValue The magnitude of the complex value.

Enumeration Definitions

Enumeration definition CtlModels:

Enum string Value Description
status-only 0
direct-with-normal-security 1
sbo-with-normal-security 2
direct-with-enhanced-security 3
sbo-with-enhanced-security 4

Enumeration definition Beh:

Enum string Value Description
on 1
blocked 2
test 3
test/blocked 4
off 5

Enumeration definition Health:

Enum string Value Description
Ok 1
Warning 2
Alarm 3

Enumeration definition Mod:

Enum string Value Description
on 1
blocked 2
test 3
test/blocked 4
off 5



Annex A - Notes on Contents

Logical Device list:

This section lists the Logical Devices within the IED. The "Default NameSpace" should point to an IEC standard (for example, "IEC61850-7-4:2003"

New Logical Node list

This section lists the proprietary Logical Nodes (i.e., those whose namespace differ from the Default Namespace of teh Logical device)

Logical Device list

This section lists all of the Logical Nodes grouped by Logical Device then by function (for example, all "L" logical nodes are listed first)

Logical Node Definitions

This section lists the Data Objects within each Logical Node. It has two options depending upon the setting of a variable within the XSLT file:

Within this section are entries for pre-defined and configuration-defined values. They are listed as:

Common Data Class Definitions

This section lists the Data Object definitions found within the dataTypeTemplates section. The "Common Data Class" (CDC) name is listed as well as the specific variant name. The attributes are grouped by function and NOT necessarily by the order of the variables (although the resulting order is very close to the definitions).

Enumeration Definitions

This section list the named attribute values as well as the associated integer. The "Enumeration string" is the value appearing in the SCL file while the integer is the value served "on-the-wire"

Contents of ReadMe.txt File

The SCL-to-MICS converter is an XSLT (eXtensible Style Language for Transformation).
It executes within a browser without needing additional "plug-ins" (IE 9 and FireFox 15.0.1 tested).

To use it, follow these instructions:


The XSLT file transforms the XML file into an appropriate HTML file which approximates the format of the MICS template.
The file is plain text if you wish to modify it, but be aware that it is VERY complex.

Also, please be aware that portions of this translator were "borrowed" from Wolfgang Wimmer (ABB Switzerland).

The translator is still in draft form with a list of enhancements listed near the top of the document.

The sample file in this folder "WIMMER_FILE_ExampleFDIS2_BAM_fixed.xml" is based upon the example in Annex D.2 of 61850-6 (Edition 1).

If you find this program useful, please include the name of the authors in any derived works:

Bruce Muschlitz (EnerNex)

Wolfgang Wimmer (ABB Baden)

(unannounced company)