EIG Meter Comparison Guide

Select Features

Typical Applications

Physical Features

Display Options

Basic Measurements and Accuracy

Advanced Revenue Measurements

Logging

Power Quality

Other

I/O

Time Synchronization

Cyber Security Features

Communication

Standards Conformity

Power Supply and Environmental

Dimensions

Nexus 1500+
Typical Applications
Utility/Industrial - Power Quality Measurement
Physical Features
Mount vertically or horizontally
Display Options
Color Touchscreen
Integrated
LCD
Basic Measurements and Accuracy
% Energy Accuracy - 0.06
ANSI C12.20 Accuracy Class - 0.1 CL Certified
Current Class - Class 2 or Class 20
Current Fault Recording Peak - 80 A/Class 20
Current Pickup 5 mA/1 mA
Frequency Range - (42.5 - 69.9) Hz
Number of 3 Phase Circuits - 1
Number of Current Inputs - 4
Overload Conditions - 100 A; 10 Sec
Sampling Rate - Over 400 samples/cycle
Voltage Pickup - 5 V
Voltage Range Line to Line - (10 - 600) V AC
Advanced Revenue Measurements
Accuracy Test Pulse - 2
CT and PT Compensation
Energy Presets
Test Mode
Time of Use
Transformer and Line Loss Compensation
Logging
I/O Log
Limit Log
Memory (Max.) - 4 GB
PQ Log
Programmable Historical Logs - 8
Stored Waveform Events before FIFO (Max.) - 3199
System Events Log
Power Quality
CBEMA and SEMI F47 Monitoring
COMTRADE Waveforms
EN 50160 PQ Reporting
Flicker
Harmonics - 127th Order
IEC 61000-4-30 Class A Ed. 3 Certified
K-Factor
Programmable Alarm Alerts
Symmetrical Components and Imbalance (Voltage and Current)
TDD
THD
Transient Recording - 50 MHz
Waveform Sampling Rate - 1024 samples/cycle
Other
Custom Modbus Map
Embedded Web Server
End of Interval Pulse
Field Upgrades (V-Switches)
Phasor Measurement Unit (PMU) - P/M
Relay Logic
I/O
Analog Inputs (Max.) - 16
Analog Outputs (Max.) - 16
Digital Inputs (Max.) - 40
KYZ Pulse Outputs (Max.) - 8
Relay Outputs (Max.) - 28
Relay Outputs (Max.) - 8
Time
Synchronization
DNP Time Sync
IRIG-B
Line Frequency Sync
NTP
PTP IEEE-1588
RTC Clock Accuracy - 3.5 ppm
Cyber Security Features
128 Bit AES Encryption
Digital Firmware Signature
Encrypted User IDs and Passwords
NERC / CIP Utility Security Protocol Compliance
Password Fail Timeouts
Password Protection
Physical Seals
Programmable Port Control
Programmable Seal Switch
Role Based Authorization
Communication
2 Separately Addressable Ethernet Ports
ANSI Optical Port
Data Rates - 1 second; 2 to 20; 1 cycle
DHCP
DNP3 Level 2

Ethernet Gateway
Fiber Optic Ethernet
GE EGD
IEC 61850
IEC 61850 GOOSE
IPV4
Modbus ASCII
Modbus RTU
Modbus TCP/IP
MV90 Support
Number of Communication Ports (Max.) - 6
RJ45 Ethernet - 2
RS485 - 2
RTU Master
SNMP
USB - 1
Standards Conformity
ANSI C12.20 0.1 CL
ANSI C62.41
CE Marked - Certified
CISPR 11 Ed. 5.1
CISPR 22 Class A
FCC Part 15; Class B
IEC 61000-4-15
IEC 61000-4-30 Class A Ed. 3 Certified
IEC 61000-6-2
IEC 61000-6-4
IEC 61850 Certification
IEC 62053-22 Class - 0.2S Certified
IEC 62053-23 Reactive Energy Ed. 1
IEC 62586-2
IEEE C37.118 - PMU
REACH/RoHS Compliance
UL 61010-1
Power Supply and Environmental
Humidity - Up to 95% RH non-condensing
IP Rating Display - IP30
Power Supply Range - Option 1 (100–240) V AC @ 50/60 Hz or (100-240) V DC; Option 2 (18-60) V DC (24-48 V DC Systems); Option 3 (100-240) V AC @ 50/60 Hz
Temperature - Operating: (-20 to +70) °C/(-4 to +158) °F
Dimensions
Case Design - Plastic
Overall Size: 10.74 x 6.74 x 6.91 in/27.28 x 17.12 x 17.55 cm
Nexus 1450
Typical Applications
Utility/Industrial - Power Quality Measurement
Physical Features
Display Mounts into Existing Knockouts
Install Without Cutting Panel
Transducer with Remote Display
Display Options
Color Touchscreen
LCD
Remote
Basic Measurements and Accuracy
% Energy Accuracy - 0.06
ANSI C12.20 Accuracy Class - 0.1 CL
Current Class - Class 20 and 2 in one configuration
Current Fault Recording Peak - 80 A
Current Pickup - 1 mA
Frequency Range - Nominal (42.5 - 69.9) Hz; Wide Band (20 - 500) Hz
Number of 3 Phase Circuits - 1
Number of Current Inputs - 4
Overload Conditions - 100 A; 10 Sec
Sampling Rate - Over 400 samples/cycle
Voltage Pickup - 5 V
Voltage Range Line to Line - (20 - 720) V AC
Advanced Revenue Measurements
Accuracy Test Pulse - 2
Time of Use
Transformer and Line Loss Compensation
Logging
Core Log with 172 Automatic Parameters
I/O Log
Limit Log
Memory (Max.) - 1.2 GB
PQ Log
Programmable Historical Logs - 8
Stored Waveform Events before FIFO (Max.) - 5461
System Events Log
Power Quality
CBEMA and SEMI F47 Monitoring
EN 50160 PQ Reporting
Flicker
Harmonics - 127th Order
IEC 61000-4-30 Class A Ed. 3 Certified
IEEE 519
K-Factor
Programmable Alarm Alerts
Symmetrical Components and Imbalance (Voltage and Current)
TDD
THD
Waveform Sampling Rate - 1024 samples/cycle
Other
Custom Modbus Map
Embedded HTML5-based Web Server with Waveform Analysis
End of Interval Pulse
Field Upgrades (V-Switches)
Relay Logic
I/O
Analog Inputs (Max.) - 32
Analog Outputs (Max.) - 16
Digital Inputs (Max.) - 40
KYZ Pulse Outputs (Max.) - 18
Relay Outputs (Max.) - 16
Time
Synchronization
DNP Time Sync
IRIG-B
Line Frequency Sync
NTP
RTC Clock Accuracy - 20 ppm
Cyber Security Features
128 Bit AES Encryption
Digital Firmware Signature
Encrypted User IDs and Passwords
NERC / CIP Utility Security Protocol Compliance
Password Fail Timeouts
Password Protection
Physical Seals
Programmable Port Control
Role Based Authorization
Communication
2 Separately Addressable Ethernet Ports
Data Rates - 1 second; 2 to 20; 1 cycle
DHCP
DNP3 Level 2

Fiber Optic Ethernet
GE EGD
IEC 61850
IEC 61850 GOOSE
IPV4
IPV6
Modbus ASCII
Modbus RTU
Modbus TCP/IP
MV90 Support
Number of Communication Ports (Max.) - 6
Number of Simultaneous Communication Connections - 6
RJ45 Ethernet - 1
RS232 - 1
RS485 - 4
RTU Master
Standards Conformity
ANSI C12.20 0.1 CL
CE Marked
CISPR 11
EN/IEC 61000-3-2 Class A
EN/IEC 61000-3-3
ICES 001 2006
IEC 61000-4-15
IEC 61000-4-30 Class A Ed. 3 Certified
IEC 62053-22 Class - 0.2S
IEC 62053-23 Reactive Energy - Class 2 Ed. 1
IEC 62586-2
IEEE 519
REACH/RoHS Compliance
UL 61010-1
Power Supply and Environmental
Humidity - Up to 95% RH non-condensing
IP Rating Display - IP30
IP Rating Meter - IP65
Power Supply Range - Option 1 (96-276) V @ 50/60 Hz or DC; Option 2 (18-60) V DC
Temperature - Operating: (-25 to +70) °C/(-32 to +158) °F
Dimensions
Case Design - Metal
Overall Size - 7.25 x 10.70 x 3.74 in/18.41 x 27.19 x 9.51 cm
Nexus 1252
Typical Applications
Utility/Industrial - Power Quality Measurement
Physical Features
Display Mounts into Existing Knockouts
Install Without Cutting Panel
Transducer with Remote Display
Display Options
LED
Remote
Basic Measurements and Accuracy
% Energy Accuracy - 0.06
ANSI C12.20 Accuracy Class - 0.2 CL
Current Class - Class 10; 2; or 0.5 (2 and 0.5 are special order)
Current Fault Recording Peak - 60 A
Current Pickup 5 mA/1 mA
Frequency Range - (20 - 65) Hz
Number of 3 Phase Circuits - 1
Number of Current Inputs - 4
Overload Conditions - 100 A; 10 Sec
Sampling Rate - Over 400 samples/cycle
Voltage Range Line to Line - 300 V (Standard; for use with PTs); 600 V (Option G)
Advanced Revenue Measurements
Accuracy Test Pulse
CT and PT Compensation
Time of Use
Transformer and Line Loss Compensation
Logging
I/O Log
Limit Log
Memory (Max.) - 4 MB
PQ Log
Programmable Historical Logs - 2
Stored Waveform Events before FIFO (Max.) - 95
System Events Log
Power Quality
CBEMA and SEMI F47 Monitoring
COMTRADE Waveforms
EN 50160 PQ Reporting
Flicker
Harmonics - 255th Order
IEC 61000-4-30 Class A Ed. 3
K-Factor
Programmable Alarm Alerts
Symmetrical Components and Imbalance (Voltage and Current)
TDD
THD
Waveform Sampling Rate - 512 samples/cycle
Other
Custom Modbus Map
Embedded Web Server
End of Interval Pulse
Field Upgrades (V-Switches)
Relay Logic
I/O
Analog Inputs (Max.) - 32
Analog Outputs (Max.) - 32
Digital Inputs (Max.) - 40
KYZ Pulse Outputs (Max.) - 16
Relay Outputs (Max.) - 16
Time
Synchronization
DNP Time Sync
IRIG-B
Line Frequency Sync
NTP
RTC Clock Accuracy - 20 ppm
Cyber Security Features
Password Protection
Physical Seals
Programmable Port Control
Programmable Seal Switch
Communication
Data Rates - 1 cycle; 1 second; 200 ms
DHCP
DNP3 Level 2

Ethernet Gateway
GE EGD
IPV4
Modbus ASCII
Modbus RTU
Modbus TCP/IP
MV90 Support
Number of Communication Ports (Max.) - 4
Number of Simultaneous Communication Connections - 4
RJ45 Ethernet - 1
RS232 - 1
RS485 - 4
RTU Master
Standards Conformity
ANSI C12.20 0.2 CL
CE Marked
IEC 62053-22 Class - 0.2S
UL 61010-1
Power Supply and Environmental
Humidity - Up to 95% RH non-condensing
Power Supply Range - Option 1 120 V AC/DC (-20%) to 230 V AC (+20%); Option 2 24 V DC (-20%) to 48 V DC (+20%)
Temperature - Operating: (-40 to +70) °C/(-40 to +158) °F
Dimensions
Case Design - Metal
Overall Size - 3.4H x 7.3W x 10.5L in/8.6 x 18.5 x 26.6 cm
Nexus 1272
Typical Applications
Utility/Industrial Revenue Metering & Power Quality
Physical Features
Install Without Cutting Panel
Display Options
Integrated
LCD
Programmable
Basic Measurements and Accuracy
% Energy Accuracy - 0.06
ANSI C12.20 Accuracy Class - 0.2 CL
Current Class - Class 20; 10; or 2
Current Pickup 5 mA/1 mA
Overload Conditions - 100 A; 10 Sec
Sampling Rate - Over 400 samples/cycle
Voltage Pickup - 2 V
Voltage Range Line to Line - Option S: 600; Option LV: 120 V
Advanced Revenue Measurements
Accuracy Test Pulse
CT and PT Compensation
Energy Presets
Test Mode
Time of Use
Transformer and Line Loss Compensation
Logging
I/O Log
Limit Log
Memory (Max.) - 4 MB
PQ Log
Programmable Historical Logs - 2
Stored Waveform Events before FIFO (Max.) - 95
System Events Log
Power Quality
CBEMA and SEMI F47 Monitoring
COMTRADE Waveforms
EN 50160 PQ Reporting
Flicker
Harmonics - 255th Order
IEC 61000-4-30 Class A Ed. 3
K-Factor
Programmable Alarm Alerts
Symmetrical Components and Imbalance (Voltage and Current)
TDD
THD
Waveform Sampling Rate - 512 samples/cycle
Other
Custom Modbus Map
Embedded Web Server
End of Interval Pulse
Field Upgrades (V-Switches)
Relay Logic
I/O
Analog Inputs (Max.) - 32
Analog Outputs (Max.) - 32
Digital Inputs (Max.) - 40
KYZ Pulse Outputs (Max.) - 20
Relay Outputs (Max.) - 16
Time
Synchronization
DNP Time Sync
IRIG-B
Line Frequency Sync
RTC Clock Accuracy - 1 second per Month
Cyber Security Features
Password Protection
Physical Seals
Programmable Port Control
Programmable Seal Switch
Communication
ANSI Optical Port
Data Rates - 1 cycle; 1 second; 200 ms
DHCP
DNP3 Level 2

Ethernet Gateway
GE EGD
IPV4
Modbus ASCII
Modbus RTU
Modbus TCP/IP
MV90 Support
Number of Communication Ports (Max.) - 5
Number of Simultaneous Communication Connections - 5
RJ45 Ethernet - 1
RS485 - 2
RTU Master
Standards Conformity
ANSI C12.20 0.2 CL and C12.1
IEC 60687 Certified
IEC 62053-11
IEC 62053-22 Class - 0.2S Certified
IS 14967
MC Canada Approval
Power Supply and Environmental
Humidity - Up to 95% RH non-condensing
Power Supply Range - Option 1 - (102 to 270) V AC/DC @50/60 Hz; Option 2 - (18 to 60) V DC
Temperature - Operating: (-40 to +85) °C/(-40 to +185) °F; Display: (-20 to +60) °C/(-4 to +140) °F
Dimensions
Case Design - Metal/Plastic
Legacy Switchboard: 16” W x 14” D x 11” H/ 40.64 cm x 35.56 cm x 28 cm
NEMA 4X Rated Cover for Switchboard
Overall Size - Socket: 13” W x 10” D x 11” H/33.02 cm x 25.40 cm x 28 cm
Switchboard (SWB3): H10.37" x W7.85" x D8.97"
Nexus 1262
Typical Applications
Utility/Industrial Revenue Metering
Physical Features
Install Without Cutting Panel
Display Options
Integrated
LCD
Programmable
Basic Measurements and Accuracy
% Energy Accuracy - 0.06
ANSI C12.20 Accuracy Class - 0.2 CL
Current Class - Class 20; 10; or 2
Current Pickup 5 mA/1 mA
Number of Current Inputs - 2 or 3 depending on form
Overload Conditions - 100 A; 10 Sec
Sampling Rate - Over 400 samples/cycle
Voltage Pickup - 2 V
Voltage Range Line to Line - Option S: 600; Option LV: 120 V
Advanced Revenue Measurements
Accuracy Test Pulse
CT and PT Compensation
Energy Presets
Test Mode
Time of Use
Transformer and Line Loss Compensation
Logging
I/O Log
Limit Log
Memory (Max.) - 2 MB
Programmable Historical Logs - 2
System Events Log
Power Quality
COMTRADE Waveforms
Harmonics - 128th Order
Programmable Alarm Alerts
Symmetrical Components and Imbalance (Voltage and Current)
THD
Other
Custom Modbus Map
Embedded Web Server
End of Interval Pulse
Field Upgrades (V-Switches)
Relay Logic
I/O
Analog Inputs (Max.) - 32
Analog Outputs (Max.) - 32
Digital Inputs (Max.) - 40
KYZ Pulse Outputs (Max.) - 20
Relay Outputs (Max.) - 16
Time
Synchronization
DNP Time Sync
IRIG-B
Line Frequency Sync
RTC Clock Accuracy - 1 second per Month
Cyber Security Features
Password Protection
Physical Seals
Programmable Port Control
Programmable Seal Switch
Communication
ANSI Optical Port
Data Rates - 1 cycle; 1 second; 200 ms
DHCP
DNP3 Level 2

Ethernet Gateway
GE EGD
IPV4
Modbus ASCII
Modbus RTU
Modbus TCP/IP
MV90 Support
Number of Communication Ports (Max.) - 5
Number of Simultaneous Communication Connections - 5
RJ45 Ethernet - 1
RS485 - 2
RTU Master
Standards Conformity
ANSI C12.20 0.2 CL and C12.1
IEC 60687 Certified
IEC 62053-11
IEC 62053-22 Class - 0.2S Certified
IS 14967
MC Canada Approval
Power Supply and Environmental
Humidity - Up to 95% RH non-condensing
Power Supply Range - Option 1 - (102 to 270) V AC/DC @50/60 Hz; Option 2 - (18 to 60) V DC
Temperature - Operating: (-40 to +85) °C/(-40 to +185) °F; Display: (-20 to +60) °C/(-4 to +140) °F
Dimensions
Case Design - Metal/Plastic
Legacy Switchboard: 16” W x 14” D x 11” H/ 40.64 cm x 35.56 cm x 28 cm
NEMA 4X Rated Cover for Switchboard
Overall Size - Socket: 13” W x 10” D x 11” H/33.02 cm x 25.40 cm x 28 cm
Switchboard (SWB3): H10.37" x W7.85" x D8.97"
Shark 270
Typical Applications
Utility/Industrial Revenue Metering
Physical Features
9S; 36S; 45S; 9A; SWB3
Install Without Cutting Panel
Display Options
Integrated
LCD
Programmable
Basic Measurements and Accuracy
% Energy Accuracy - 0.1
ANSI C12.20 Accuracy Class - 0.1 CL Certified
Current Class - Class 2 or Class 10
Current Pickup - Class 20 (5 mA); Class 2 (1 mA)
Extended Frequency Measurement Accuracy +/- 0.007 Hz
Frequency Range - (45 - 65) Hz
Number of 3 Phase Circuits - 1
Number of Current Inputs - 3
Sampling Rate - Over 400 samples/cycle
Voltage Pickup - 10 V AC; programmable
Voltage Range Line to Line - (20 - 721) V
Advanced Revenue Measurements
Accuracy Test Pulse
CT and PT Compensation
Energy Presets
Test Mode
Time of Use
Transformer and Line Loss Compensation
Logging
I/O Log
Limit Log
Memory (Max.) - 128 MB
PQ Log
Programmable Historical Logs - 6
Stored Waveform Events before FIFO (Max.) - 128
System Events Log
Power Quality
CBEMA and SEMI F47 Monitoring
COMTRADE Waveforms
Harmonics - Up to 40th Order
K-Factor
Programmable Alarm Alerts
Symmetrical Components and Imbalance (Voltage and Current)
TDD
THD
Waveform Sampling Rate - 512 samples/cycle
Other
Custom Modbus Map
Embedded HTML5-based Web Server
End of Interval Pulse
Field Upgrades (V-Switches)
Surge Suppression Technology
I/O
Analog Outputs (Max.) - 8
Digital Inputs (Max.) - 4
KYZ Pulse Outputs (Max.) - 9
Pulse Inputs (Max.) - 8
Relay Outputs (Max.) - 4
Time
Synchronization
DNP Time Sync
IRIG-B
Line Frequency Sync
NTP
RTC Clock Accuracy - Better than 15 seconds per month
Cyber Security Features
Allow/Block Lists
Digital Firmware Signature
Encrypted User IDs and Passwords
Ethernet Card Encryption; Configurable Firewalls; and Digital Firmware Signature
NERC / CIP Utility Security Protocol Compliance
Password Fail Timeouts
Password Protection
Physical Seals
Programmable Port Control
Programmable Seal Switch
Role Based Authorization
Communication
2 Separately Addressable Ethernet Ports
ANSI Optical Port
Data Rates - 100 ms and 1 second
DNP3 Level 2

IEC 61850
IPV4
IPV6
Modbus ASCII
Modbus RTU
Modbus TCP/IP
MV90 Support
Number of Communication Ports (Max.) - 4
Number of Simultaneous Communication Connections (Max.) - 24
RJ45 Ethernet - 2
RS232 - 2
RS485 - 3
Underglass 4G Cellular Modem
Standards Conformity
ANSI C12.18
ANSI C12.20 0.1 CL
CE Marked
FCC Part 15; Class B
IEC 61557-12
IEC 62053-22 Class - 0.2S Certified
IEC 62053-23 Reactive Energy - Class 2 Certified
IEEE C37.90.1
IEEE C62.41
MC Canada Approval
REACH/RoHS Compliance
Power Supply and Environmental
Humidity - Up to 95% RH non-condensing
IP Rating Meter - IP51
Power Supply Range - Dependent on voltage form; see brochure
Temperature - Storage: (-40 to +85) °C; Meter Operating: (-40 to +70) °C; Display Operating: (-30 to +60) °C
Dimensions
Case Design - Plastic
Keystone Connectors for Communication and I/O
Overall Size: Socket Form: H7" x W6.96" x D8.75"; Switchboard Form (SWB3): H10.37" x W7.85" x D8.97"
Shark 250
Typical Applications
Utility/Industrial
Physical Features
ANSI C39.1 4 in. round or IEC 96 mm DIN square form
Install Without Cutting Panel
Display Options
Integrated
LED
Basic Measurements and Accuracy
% Energy Accuracy - 0.1
ANSI C12.20 Accuracy Class - 0.1 CL Certified
Current Class - Class 2 or Class 10
Current Pickup - Class 10 (5 mA); Class 2 (1 mA)
Extended Frequency Measurement Accuracy +/- 0.007 Hz
Frequency Range - (45 - 65) Hz
Number of Current Inputs - 3
Sampling Rate - Over 400 samples/cycle
Voltage Pickup - 10 V AC; programmable
Voltage Range Line to Line - Absolute Range (0-721) V
Advanced Revenue Measurements
Accuracy Test Pulse
CT and PT Compensation
Energy Presets
Test Mode
Time of Use
Transformer and Line Loss Compensation
Logging
I/O Log
Limit Log
Memory (Max.) - 128 MB
PQ Log
Programmable Historical Logs - 6
Stored Waveform Events before FIFO (Max.) - 128
System Events Log
Power Quality
CBEMA and SEMI F47 Monitoring
COMTRADE Waveforms
Harmonics - Up to 40th Order
K-Factor
Programmable Alarm Alerts
Symmetrical Components and Imbalance (Voltage and Current)
TDD
THD
Waveform Sampling Rate - 512 samples/cycle
Other
Embedded Web Server
End of Interval Pulse
Field Upgrades (V-Switches)
I/O
Analog Outputs (Max.) - 8
Digital Inputs (Max.) - 4
KYZ Pulse Outputs (Max.) - 9
Pulse Inputs (Max.) - 8
Relay Outputs (Max.) - 4
Time
Synchronization
DNP Time Sync
Line Frequency Sync
NTP
RTC Clock Accuracy - 15 seconds per month over the temperature range is the “worst case” scenario - 6 seconds per month is typical at -15 °C to +25 °C.
Cyber Security Features
Allow/Block Lists
Encrypted User IDs and Passwords
NERC / CIP Utility Security Protocol Compliance
Password Fail Timeouts
Password Protection
Programmable Port Control
Programmable Seal Switch
Role Based Authorization
Communication
2 Separately Addressable Ethernet Ports
Data Rates - 100 ms and 1 second
DNP3 Level 2

Fiber Optic Ethernet
IEC 61850
IPV4
IPV6
IrDA Port
Modbus ASCII
Modbus RTU
Modbus TCP/IP
MV90 Support
Number of Communication Ports (Max.) - 4
Number of Simultaneous Communication Connections (Max.) - 24
RJ45 Ethernet - 2
RS232 - 2
RS485 - 1
USB - 1
Standards Conformity
ANSI C12.20 0.1 CL
CE Marked
IEC 62053-22 Class - 0.2S
IEC 62053-23 Reactive Energy - Class 2
IEEE C37.90.1
IEEE C62.41
REACH/RoHS Compliance
UL 61010-1
Power Supply and Environmental
Humidity - Up to 95% RH non-condensing
IP Rating Display - IP30
NEMA Rating - NEMA 12
Power Supply Range - Option 1 - (90-265) V AC or (100-370) V DC; Option 2 (18-60) V DC
Temperature - Storage: (-20 to +70) °C; Operating: (-20 to +70) °C
Dimensions
Case Design - Plastic
DIN-rail Mounted - Transducer Version
Overall Size - H4.85" x W4.85" x D4.25" in.
Shark 200
Typical Applications
Utility/Industrial
Physical Features
ANSI C39.1 4 in. round or IEC 96 mm DIN square form
Install Without Cutting Panel
Display Options
Integrated
LED
Basic Measurements and Accuracy
% Energy Accuracy - 0.2
ANSI C12.20 Accuracy Class - 0.2 CL Certified
Current Class - Class 2 or Class 10
Current Pickup - Class 10 (5 mA); Class 2 (1 mA)
Extended Frequency Measurement Accuracy +/- 0.007 Hz
Frequency Range - (45 - 65) Hz
Number of 3 Phase Circuits - 1
Number of Current Inputs - 3
Sampling Rate - Over 400 samples/cycle
Voltage Pickup - 10 V AC; programmable
Voltage Range Line to Line - Absolute Range (0-721) V
Advanced Revenue Measurements
Accuracy Test Pulse
CT and PT Compensation
Transformer and Line Loss Compensation
Logging
I/O Log
Limit Log
Memory (Max.) - 4 MB
PQ Log
Programmable Historical Logs - 3
Stored Waveform Events before FIFO (Max.) - 170
System Events Log
Power Quality
CBEMA and SEMI F47 Monitoring
COMTRADE Waveforms
Harmonics - Up to 40th Order
K-Factor
Programmable Alarm Alerts
Symmetrical Components and Imbalance (Voltage and Current)
TDD
THD
Waveform Sampling Rate - 512 samples/cycle
Other
Embedded Web Server
End of Interval Pulse
Field Upgrades (V-Switches)
I/O
Analog Outputs (Max.) - 8
Digital Inputs (Max.) - 4
KYZ Pulse Outputs (Max.) - 9
Pulse Inputs (Max.) - 8
Relay Outputs (Max.) - 4
Time
Synchronization
Line Frequency Sync
NTP
RTC Clock Accuracy - Max. +/-2 seconds per day at 25 °C
Cyber Security Features
Allow/Block Lists
Password Protection
Programmable Port Control
Communication
2 Separately Addressable Ethernet Ports
Data Rates - Watts; VAR; and VA; 100 ms; All other parameters; 1 second
DNP3

Fiber Optic Ethernet
IEC 61850
IPV4
IrDA Port
Modbus ASCII
Modbus RTU
Modbus TCP/IP
MV90 Support
Number of Communication Ports (Max.) - 4
Number of Simultaneous Communication Connections (Max.) - 24
RJ45 Ethernet - 2
RS485 - 1
Standards Conformity
ANSI C12.20 0.2 CL
ANSI C12.41
CE Marked
EN 61000-6-2
EN 61000-6-4
FCC Part 15; Class B
IEC 61850 Certification
IEC 62053-22 Class - 0.2S Certified
IEC 62053-23 Reactive Energy - Class 2
IEEE C37.90.1
IEEE C62.41
NY State Approved for Residential Metering
REACH/RoHS Compliance
UL 61010-1
Power Supply and Environmental
Humidity - Up to 95% RH non-condensing
IP Rating Display - IP30
NEMA Rating - NEMA 12
Power Supply Range - Option 1 - (90-265) V AC or (100-370) V DC; Option 2 (18-60) V DC
Temperature - Storage: (-20 to +70) °C; Operating: (-20 to +70) °C
Dimensions
Case Design - Plastic
DIN-rail Mounted - Transducer Version
Overall Size - H4.85" x W4.85" x D4.25" in.
Shark 100
Typical Applications
Utility/Industrial
Physical Features
ANSI C39.1 4 in. round or IEC 96 mm DIN square form
Install Without Cutting Panel
Display Options
Integrated
LED
Basic Measurements and Accuracy
% Energy Accuracy - 0.2
ANSI C12.20 Accuracy Class - 0.2 CL
Current Class - Class 2 or Class 10
Current Pickup - Class 10 (5 mA); Class 2 (1 mA)
Frequency Range - (45 - 65) Hz
Number of 3 Phase Circuits - 1
Number of Current Inputs - 3
Sampling Rate - Over 400 samples/cycle
Voltage Pickup - 20 V AC
Voltage Range Line to Line - Absolute Range (0-721) V
Advanced Revenue Measurements
Accuracy Test Pulse
Logging
Power Quality
Harmonics - 7th order (current); 3rd order (voltage)
Programmable Alarm Alerts
THD
Other
Field Upgrades (V-Switches)
I/O
KYZ Pulse Outputs (Max.) - 1
Time
Synchronization
Cyber Security Features
Password Protection
Communication
Data Rates - Watts; VAR; and VA; 100 ms; All other parameters; 1 second
DNP3
IPV4
IrDA Port
Modbus ASCII
Modbus RTU
Modbus TCP/IP
Number of Communication Ports (Max.) - 2
RS485 - 1
Standards Conformity
ANSI C12.20 0.2 CL
CE Marked
IEC 62053-22 Class - 0.2S
IEC 62053-23 Reactive Energy - Class 2
IEEE C37.90.1
IEEE C62.41
REACH/RoHS Compliance
UL 61010-1
Power Supply and Environmental
Humidity - Up to 95% RH non-condensing
IP Rating Display - IP30
NEMA Rating - NEMA 12
Power Supply Range - Option 1 - (90-265) V AC or (100-370) V DC; Option 2 (18-60) V DC
Storage: (-20 to +70) °C; Operating: (-20 to +70) °C
Dimensions
Case Design - Plastic
DIN-rail Mounted - Transducer Version
Overall Size - H4.85" x W4.85" x D4.25" in.
Shark 100B
Typical Applications
Commercial Energy Management
Physical Features
ANSI C39.1 4 in. round or IEC 96 mm DIN square form
Install Without Cutting Panel
Display Options
Integrated
LED
Basic Measurements and Accuracy
% Energy Accuracy - 0.2
ANSI C12.20 Accuracy Class - 0.2 CL
Current Class - Class 2 or Class 10
Current Pickup - 5 mA
Current Pickup - Class 10 (5 mA); Class 2 (1 mA)
Frequency Range - (45 - 65) Hz
Number of 3 Phase Circuits - 1
Number of Current Inputs - 3
Sampling Rate - Over 400 samples/cycle
Voltage Pickup - 20 V AC
Voltage Range Line to Line - Absolute Range (0-721) V
Advanced Revenue Measurements
Accuracy Test Pulse
Logging
Power Quality
Harmonics - 7th order (current); 3rd order (voltage)
Programmable Alarm Alerts
THD
Other
Embedded Web Server
I/O
KYZ Pulse Outputs (Max.) - 1
Time
Synchronization
Cyber Security Features
Password Protection
Communication
BACnet/IP
Data Rates - Watts; VAR; and VA; 100 ms; All other parameters; 1 second
IPV4
IrDA Port
Modbus ASCII
Modbus RTU
Modbus TCP/IP
Number of Communication Ports (Max.) - 2
RJ45 Ethernet - 1
Standards Conformity
CE Marked
IEC 62053-22 Class - 0.2S
IEC 62053-23 Reactive Energy - Class 2
IEEE C37.90.1
IEEE C62.41
REACH/RoHS Compliance
UL 61010-1
Power Supply and Environmental
Humidity - Up to 95% RH non-condensing
IP Rating Display - IP30
NEMA Rating - NEMA 12
Power Supply Range - Option 1 - (90-265) V AC; Option 2 (18-60) V DC
Temperature - Storage: (-20 to +70) °C; Operating: (-20 to +70) °C
Dimensions
Case Design - Plastic
DIN-rail Mounted - Transducer Version
Overall Size - H4.85" x W4.85" x D4.25" in.
Shark 50
Typical Applications
Industrial Panel Boards
Physical Features
ANSI C39.1 4 in. round or IEC 96 mm DIN square form
Install Without Cutting Panel
Display Options
Integrated
LED
Basic Measurements and Accuracy
% Energy Accuracy - 0.5
ANSI C12.20 Accuracy Class - 0.5 CL
Current Class - Class 10
Current Pickup - 5 mA
Frequency Range - (45 - 65) Hz
Number of 3 Phase Circuits - 1
Number of Current Inputs - 3
Sampling Rate - Over 400 samples/cycle
Voltage Pickup - 20 V AC
Voltage Range Line to Line - (20 - 721) V
Advanced Revenue Measurements
Logging
Power Quality
Other
Field Upgrades (V-Switches)
I/O
KYZ Pulse Outputs (Max.) - 1
Time
Synchronization
Cyber Security Features
Password Protection
Communication
Data Rates - 1 second
IPV4
Modbus ASCII
Modbus RTU
Number of Communication Ports (Max.) - 1
Number of Simultaneous Communication Connections - 1
RS485 - 1
Standards Conformity
ANSI C12.20 0.5 CL
CE Marked
IEC 62053-22 Class - 0.5S Certified
IEEE C37.90.1
IEEE C62.41
REACH/RoHS Compliance
UL 61010-1
Power Supply and Environmental
Humidity - Up to 95% RH non-condensing
IP Rating Display - IP30
NEMA Rating - NEMA 12
Power Supply Range - (90-265) V AC
Storage: (-20 to +70) °C; Operating: (-20 to +70) °C
Dimensions
Case Design - Plastic
Overall Size - H4.85" x W4.85" x D4.25" in.
Shark 50B
Typical Applications
Commercial Energy Management
Physical Features
ANSI C39.1 4 in. round or IEC 96 mm DIN square form
Install Without Cutting Panel
Display Options
Integrated
LED
Basic Measurements and Accuracy
% Energy Accuracy - 0.5
ANSI C12.20 Accuracy Class - 0.5 CL
Current Class - Class 10
Current Pickup - 5 mA
Frequency Range - (45 - 65) Hz
Number of 3 Phase Circuits - 1
Number of Current Inputs - 3
Sampling Rate - Over 400 samples/cycle
Voltage Pickup - 20 V AC
Voltage Range Line to Line - Absolute Range (0-721) V
Advanced Revenue Measurements
Accuracy Test Pulse
Logging
Power Quality
Other
Embedded Web Server
I/O
Time
Synchronization
Cyber Security Features
Password Protection
Communication
BACnet MS/TP
Data Rates - all parameters every 60 cycles
IPV4
Modbus RTU
Modbus TCP/IP
Number of Communication Ports (Max.) - 2
RJ45 Ethernet - 1
RS485 - 1
Standards Conformity
CE Marked
IEC 62053-22 Class - 0.5S Certified
IEEE C37.90.1
IEEE C62.41
REACH/RoHS Compliance
UL 61010-1
Power Supply and Environmental
Humidity - Up to 95% RH non-condensing
IP Rating Display - IP30
NEMA Rating - NEMA 12
Power Supply Range - (90-265) V AC
Storage: (-20 to +70) °C; Operating: (-20 to +70) °C
Dimensions
Case Design - Plastic
DIN-rail Mounted - Transducer Version
Overall Size - H4.85" x W4.85" x D4.25" in.
Shark 200S
Typical Applications
Commercial Submetering
Physical Features
Wall Mountable
Display Options
Integrated
LED
Basic Measurements and Accuracy
% Energy Accuracy - 0.2
ANSI C12.20 Accuracy Class - 0.2 CL Certified
Current Class - Class 2 or Class 10
Current Pickup - Class 10 (5 mA); Class 2 (1 mA)
Extended Frequency Measurement Accuracy +/- 0.007 Hz
Frequency Range - (45 - 65) Hz
Number of 3 Phase Circuits - 1
Number of Current Inputs - 3
Overload Conditions - 100 A; 10 Sec
Sampling Rate - Over 400 samples/cycle
Voltage Pickup - 10 V AC
Voltage Range Line to Line - (0 - 721) V
Advanced Revenue Measurements
Accuracy Test Pulse
CT and PT Compensation
Transformer and Line Loss Compensation
Logging
Limit Log
Memory (Max.) - 2 MB
Programmable Historical Logs - 3
System Events Log
Power Quality
Programmable Alarm Alerts
Other
I/O
Time
Synchronization
Line Frequency Sync
Cyber Security Features
Password Protection
Communication
Data Rates - 100 ms and 1 second
DNP3
IPV4
IrDA Port
Modbus ASCII
Modbus RTU
Modbus TCP/IP
Number of Communication Ports (Max.) - 3
Number of Simultaneous Communication Connections - 2
RJ45 Ethernet - 1
RS485 - 1
WiFi - 802.11 WiFi
Standards Conformity
ANSI C12.20 0.2 CL and C12.1 Certified
ANSI C62.41
CE Marked
ERM: Wideband transmission system operating in the 2.4GHz ISM band using wideband modulation techniques. V1.6.1 (WiFi Module) Information technology equipment-Safety-part 1: General requirements: 2001
FCC Part 15; Class B
IEC 62053-22 Class - 0.2S Certified
IEC 62053-23 Reactive Energy - Class 2 Ed. 1
IEEE C37.90.1
IEEE C62.41
REACH/RoHS Compliance
UL 61010-1
Power Supply and Environmental
Humidity - Up to 95% RH non-condensing
IP Rating Display - IP30
Power Supply Range - (90 to 400) V AC or (100 to 370) V DC; Universal AC/DC Supply
Temperature - Storage: (-20 to +70) °C /(-4 to +158) °F; Operating: (-20 to +70) °C /(-4 to +158) °F
Dimensions
Case Design - Plastic
Overall Size - H7.90" x W7.53" x D3.11"
Shark 100S
Typical Applications
Commercial Submetering
Physical Features
Wall Mountable
Display Options
Integrated
LED
Basic Measurements and Accuracy
% Energy Accuracy - 0.2
ANSI C12.20 Accuracy Class - 0.2 CL
Current Class - Class 2 or Class 10
Current Pickup - Class 10 (5 mA); Class 2 (1 mA)
Frequency Range - (45 - 65) Hz
Number of 3 Phase Circuits - 1
Number of Current Inputs - 3
Overload Conditions - 100 A; 10 Sec
Sampling Rate - Over 400 samples/cycle
Voltage Pickup - 10 V AC
Voltage Range Line to Line - (0 - 721) V
Advanced Revenue Measurements
Accuracy Test Pulse
Logging
Power Quality
Harmonics - 7th order (current); 3rd order (voltage)
Programmable Alarm Alerts
THD
Other
Field Upgrades (V-Switches)
I/O
Time
Synchronization
Cyber Security Features
Password Protection
Communication
Data Rates - 100 ms and 1 second
DNP3
IPV4
IrDA Port
Modbus ASCII
Modbus RTU
Modbus TCP/IP
Number of Communication Ports (Max.) - 3
Number of Simultaneous Communication Connections - 2
RJ45 Ethernet - 1
RS485 - 1
WiFi - 802.11 WiFi
Standards Conformity
ANSI C12.20 0.2 CL
CE Marked
ERM: Wideband transmission system operating in the 2.4GHz ISM band using wideband modulation techniques. V1.6.1 (WiFi Module) Information technology equipment-Safety-part 1: General requirements: 2001
IEC 62053-22 Class - 0.2S
IEC 62053-23 Reactive Energy - Class 2 Ed. 1
IEEE C37.90.1
IEEE C62.41
REACH/RoHS Compliance
UL 61010-1
Power Supply and Environmental
Humidity - Up to 95% RH non-condensing
IP Rating Display - IP30
Power Supply Range - (90 to 400) V AC or (100 to 370) V DC; Universal AC/DC Supply
Temperature - Storage: (-20 to +70) °C /(-4 to +158) °F; Operating: (-20 to +70) °C /(-4 to +158) °F
Dimensions
Case Design - Plastic
Overall Size - H7.90" x W7.53" x D3.11"
MP200
Typical Applications
Multi-circuit Submetering
Physical Features
Multi-circuit Design
Display Options
Color Touchscreen
LCD
Remote
Basic Measurements and Accuracy
% Energy Accuracy - 0.5
ANSI C12.20 Accuracy Class - 0.5 CL
Current Class - Class 2 or Class 10
Current Pickup - Class 10 (5 mA); Class 2 (1 mA)
Frequency Range - (45 - 65) Hz
Number of 3 Phase Circuits - 8
Number of Current Inputs - 24
Sampling Rate - Over 400 samples/cycle
Voltage Pickup - 20 V AC
Voltage Range Line to Line - Absolute Range (0-721) V
Advanced Revenue Measurements
Accuracy Test Pulse
Logging
I/O Log
Limit Log
Memory (Max.) - 32 MB
Programmable Historical Logs - 2
System Events Log
Power Quality
Programmable Alarm Alerts
Other
Field Upgrades (V-Switches)
I/O
KYZ Inputs (Max.) - 4
Relay Outputs (Max.) - 2
Time
Synchronization
RTC Clock Accuracy - ±3.5 ppm max. (±0.3024 second/day) over the rated temperature range
Cyber Security Features
Password Protection
Communication
Data Rates - 1 second
IPV4
Modbus ASCII
Modbus RTU
Modbus TCP/IP
Number of Communication Ports (Max.) - 4
Number of Simultaneous Communication Connections - 3
RJ45 Ethernet - 1
RS485 - 2
USB - 1
WiFi - 802.11 WiFi
Standards Conformity
ANSI C12.20 0.5 CL
CE Marked
ERM: Wideband transmission system operating in the 2.4GHz ISM band using wideband modulation techniques. V1.6.1 (WiFi Module) Information technology equipment-Safety-part 1: General requirements: 2001
IEC 62053-22 Class - 0.5S
REACH/RoHS Compliance
UL 61010-1
Power Supply and Environmental
Humidity - Up to 95% RH non-condensing
Power Supply Range - (90-300) V AC @ 50/60 Hz
Temperature - Storage: (-20 to +70) °C / (-4 to +158) °F; Operating: (-20 to +60) °C / (-4 to +140) °F
Dimensions
Case Design - Metal
Overall Size - H7.60" x W11.28" x D3.18"
ST40
Typical Applications
Commercial/Industrial Submetering
Physical Features
Compact Size; DIN-rail Mounting
Display Options
Integrated
LED
Basic Measurements and Accuracy
% Energy Accuracy - 0.2
ANSI C12.20 Accuracy Class - 0.2 CL
Current Class - Class 2 or Class 10
Current Pickup - Class 10 (5 mA); Class 2 (1 mA)
Frequency Range - (45 - 65) Hz
mV CTs - 0.333 V or Rogowski Coil CTs
Number of 3 Phase Circuits - 1
Number of Current Inputs - 3
Sampling Rate - Over 400 samples/cycle
Voltage Pickup - 20 V AC
Voltage Range Line to Line - Absolute Range (0-721) V
Advanced Revenue Measurements
Accuracy Test Pulse
CT and PT Compensation
Transformer and Line Loss Compensation
Logging
Limit Log
Memory - Extensive Memory
Programmable Historical Logs - 3
Stored Waveform Events before FIFO (Max.) - 128
System Events Log
Power Quality
CBEMA and SEMI F47 Monitoring
Harmonics - 40th Order
Programmable Alarm Alerts
THD
Waveform Sampling Rate - 512 samples/cycle
Other
Field Upgrades (V-Switches)
I/O
Time
Synchronization
Line Frequency Sync
RTC Clock Accuracy - Max. +/-2 seconds per day at 25 °C
Cyber Security Features
Password Protection
Communication
BACnet/IP
Data Rates - 100 ms and 1 second
DNP3
IPV4
Modbus ASCII
Modbus RTU
Modbus TCP/IP
MV90 Support
Number of Communication Ports (Max.) - 2
Number of Simultaneous Communication Connections - 3
RJ45 Ethernet - 1
RS485 - 1
USB - 1
Standards Conformity
ANSI C12.20 0.2 CL
CE Marked
IEC 62053-22 Class - 0.2S
REACH/RoHS Compliance
UL 61010-1
Power Supply and Environmental
Humidity - Up to 95% RH non-condensing
IP Rating Display - IP30
Power Supply Range - (90-300) V AC @ 50/60 Hz
Temperature - Storage: (-20 to +70) °C; Operating: (-20 to +70) °C *;* UL certified to °65
Dimensions
Case Design - Plastic
Overall Size - H4.60" x W4.77" x D2.44"