Shark Meter Comparison Chart

HomeShark Meter Comparison Chart
 Shark 50Shark 50BShark 100Shark 100BShark 200Shark 250Shark 270
Typical Application Uses
Industrial Panel BoardsCommercial Energy Management SystemsUtility and Industrial SwitchgearCommercial Energy Management SystemsUtility and Industrial SwitchgearUtility and Industrial SwitchgearUtility and Industrial Revenue Metering
Physical Features
Form FactorANSI C39.1 (4" round form) or an IEC 92mm DIN square formANSI C39.1 (4" round form) or an IEC 92mm DIN square formANSI C39.1 (4" round form) or an IEC 92mm DIN square formANSI C39.1 (4" round form) or an IEC 92mm DIN square formANSI C39.1 (4" round form) or an IEC 92mm DIN square formANSI C39.1 (4" round form) or an IEC 92mm DIN square form9S, 36S, 45S, 9A, SWB3
Can be installed without cutting Switchboard panel
Power On LED
Display Options
LCD
LED
(Integrated display)

(Integrated display)

(Integrated display)

(Integrated display)

(Integrated display)

(Integrated display)
Easy to read
Optical Port/USB Port Shared
(USB Port)

(Optical Port)

Meter Features

Basic Measurements and Accuracy
ANSI C12.20 Accuracy Class0.5S0.5S0.2S0.2S0.2S0.1S0.1S
Stated Energy Accuracy %0.50.50.20.20.20.10.1
Number of 3 Phase Circuits1111111
Current Class 2 and Class 20 CombinationClass 10Class 10Class 10 or Class 2Class 10 or Class 2Class 10 or Class 2Class 10 or Class 2Class 20 or Class 2
Number of Current inputs3333333
Frequency Range45 - 65 Hz45 - 65 Hz45 - 65 Hz45 - 65 Hz45 - 65 Hz45 - 65 Hz45 - 65 Hz
Voltage Range 0-690V Line to Line20 - 721V Line to Lineup to 20 - 721V Line to Line20 - 721V Line to Lineup to 20 - 721V Line to Line0 - 721V Line to Line0 - 721V Line to Line0 - 720V Line to Line
Voltage Pickup20 V AC20 V AC20 V AC20 V AC20 V AC20 V AC
Current Pickup5 mAClass 10 (5 mA) Class 2 (1 mA)Class 10 (5 mA) Class 2 ( 1 mA)Class 10 (5 mA) Class 2 ( 1 mA)Class 20 (5 mA) Class 2 (1 mA)
Sampling RateOver 400 samples/cycleOver 400 samples/cycleOver 400 samples/cycleOver 400 samples/cycleOver 400 samples/cycleOver 400 samples/cycleUp to 512 samples per cycle
Advanced Revenue Measurements
Test Mode
Energy Presets
Transformer and Line Loss compensation
CT & PT Compensation
Time of Use
Accuracy Test Pulse
Logging
4GB Memory
(up to 4 MB)

(up to 128 MB)

(up to 128 MB)
8 Programmable Historical LogsUp to 3 Historical LogsUp to 6 Historical LogsUp to 6 Historical Logs
Limit Log
I/O Log
PQ Log
System Events Log
8,000+ Max Stored Waveform Events (before FIFO)170319319
Power Quality
Programmable Alarm Alerts
THD
TDD
K-Factor
Harmonics7th order for current and up
to the 3rd order for voltage
7th order for current and up
to the 3rd order for voltage

(40th Order)

(40th Order)

(40th Order)
IEC 61000-4-7 Harmonic Measurements
Waveform Sampling Rate512 samples/cycle (V6)512 samples/cycle (V4)512 samples/cycle (V5)
CBEMA and SEMI F47 MonitoringCBEMA or SEMI F47CBEMA
Symmetrical Components and Imbalance (Voltage and Current)
Other
Field Upgrades (V-Switches)
Advanced Web Server with Waveform AnalysisWeb ServerWeb ServerWeb Server
I/O
Digital Inputs
(8-O)

(8-O)

(8-O)
KYZ Inputs
(8-O)

(8-O)

(8-O)
Relay Outputs
(4-O)

(4-O)

(4-O)
KYZ Pulse Outputs
(1-S)

(1-O)

(1-S)

(8-O)(1-S)

(8-O)(1-S)

(8-O)(1-S)
Analog Outputs
(8-O)

(8-O)

(8-O)
Expandable I/O using Modules
Time Synchronization
NTP
Line Frequency Sync
End of Interval Pulse
RTC Clock AccuracyMax. +/-2 seconds per day at 25 °C15 seconds per month over the temperature range is the “worst case” scenario - 6 secondsper month is typical at -15 oC to +25 °C.Internal clock - accuracy better than 15 seconds per month.
Cyber Security Features
Password Fail Timeouts Eliminate Brute Force Hacking
Role Based Permission access
10 User IDs and Passwords - Up to 30 Characters
NERC / SIP Uility Security Protocol Compliance
FIPS 140 Cyber Secuity Compliance
Physical security sealing points preventing tampering
Revenue lock
Programmable web protocol and port control
Communication
2 Separately Addressable Ethernet Ports using unique IP address1
Fiber Optic
Optical Ports/IRDA PortIRDAIRDAIRDA PortOptical Port
6 simultaneously operating communication portsIf two (2) Ethernet card 24 simultaneous Modbus TCP/IP and up to 10 simultaneous DNP connection and one (1) RS485 connection either Modbus or DNP3If two (2) INP100S Ethernet card 24 simultaneous Modbus TCP/IP and up to 10 simultaneous DNP connection and one (1) RS485 connection either Modbus or DNP3 or if one (1) INP100s Ethernet card 12 simultaneous Modbus TCP/IP and up to 5 simultaneous DNP connection and one (1) RS485 connection either Modbus or DNP3 + one (1) INP300S it can communicate with IEC 61850 + Modbus TCP simultaneously and 5 MMS ClientFor socket type one (1) INP100s Ethernet card 12 simultaneous Modbus TCP/IP and up to 5 simultaneous DNP connection + one (1) RS485 connection either Modbus or DNP3 or one (1) INP300S it can communicate with IEC 61850 + Modbus TCP simultaneously and 5 MMS Client one (1) RS485 connection either Modbus or DNP3
Max # of Communication Ports1222444
Modbus RTU, ASCII
Modbus TCP/IP
DNP3 Level 2 communication with secure DNP stackDNP3DNP3DNP3
(DNP3 Level 2)

(DNP3 Level 2)
IEC61850
BACnet/MSTP
Bacnet/IP
Speak SCADA or other communication systems, simultaneously
Emails on Alarm
RS485
(1-O)

(1-S)

(1-S)

(1-S)

(1-S)(1-O)
RS232
(1-O)
USB
RJ45 Ethernet(1-S)
(1-S)

(2-O)

(2-O)
Fiber Optic Output ST terminated
(2-O)

(2-O)
Fiber Optic Output Versatile Link terminated
(2-O)

(2-O)
4G Cellular
(1-O)
ITIC CBEMA Curve and SEMI F47CBEMA or SEMI F47CBEMA
MV90 Support
Comtrade Waveforms
IPV4 with DHCPIPV4
Update Rate1 secondAll Parameters Every 60 cycles100 ms and 1 secondWatts, VAR and VA-100 ms
All other parameters-1 second
100 ms and 1 second100 ms and 1 second100 ms and 1 second
Web Server
Html 5 Interactive Web ServerSupport Web ServerSupport Web ServerSupport Web Server
HTTPS web pageSupport Web Page
Standards Conformity
UL6010UL 61010-1UL 61010-1UL 61010-1UL 61010-1UL/IEC 61010-1UL/IEC 61010-1
ANSI C12.20.1 Class 0.1ANSI C12.20 (0.5% Accuracy)ANSI C12.20 (0.2% Accuracy)ANSI C12.20 (0.2% Accuracy)ANSI C12.20 (0.2% Accuracy)
IEC 61557-12
IEC 62053-22 0.2% EnergyIEC 62053-22 (0.5% Accuracy)IEC 62053-22 (0.5% Accuracy)IEC 62053-22 (0.2% Accuracy)IEC 62053-22 (0.2% Accuracy)
IEC 62053-24 0.5% Reactive EnergyIEC 62053-23
IEC 61000-4-7
Power Supply and Environmental
85 to 305 V AC or 100 to 140 V DC(90 to 265) Volts AC(90 to 265) Volts AC(90-265) V AC or (100-370) V DC(90 to 265) Volts AC(90 to 265) Volts AC and (100 to 370)(90 to 265) Volts AC and (100 to 370)75 to 277 V AC
75 to 400 V DC
24 to 48 V DC(18-60) V DC(18-60) V DC(18-60) V DC
TemperatureStorage: (-20 to +70) °C
Operating: (-20 to +70) °C
Storage: (-20 to +70) °C
Operating: (-20 to +70) °C
Storage: (-20 to +70) °C
Operating: (-20 to +70) °C
Storage: (-20 to +70) °C
Operating: (-20 to +70) °C
Storage: (-20 to +70) °C
Operating: (-20 to +70) °C
Operating Temperature: (-40 to +70) °C
• Display Operating Temperature: (-30 to +60) °C
Humidityto 95% RH Non-Condensingto 95% RH Non-Condensingto 95% RH Non-Condensingto 95% RH Non-Condensingto 95% RH Non-Condensingto 95% RH Non-Condensing
IP Rating MeterIP31IP30IP30IP30IP51
IP Rating DisplayIP65
Dimensions
H4.85" x W4.85" x L4.25" in.H4.85" x W4.85" x L4.25" in.H4.85" x W4.85" x L4.25" in.H4.85" x W4.85" x L4.25" in.H4.85" x W4.85" x L4.25" in.H4.85" x W4.85" x L4.25" in.A-Base Size: 14.5" W x 16" D x 11" H
Switchboard Size: 13" W x 10" D x 11" H
Din Rail Mounted
Display ANSI and DIN 96M mounted
Case DesignPlasticPlasticPlasticPlasticPlasticPlasticPlastic