ST40 Compact DIN Rail Mounted Energy and Power Quality Meter
Introduction
Power Quality Measurement
Reduce Energy Costs Using EIG’s EnergyPQA.com® System
Applications
Downloads

Introducing the ST40 DIN Rail Energy Meter
The ST40 DIN rail energy meter is one of the smallest energy and power quality meters in the world. It was designed specifically for DIN rail installation where space is at a premium. The meter provides 0.2% class energy accuracy and advanced power quality features.
Advanced Revenue Meter
- ANSI C12.20 0.2 Accuracy Class energy measurement.
- Traceable watt-hour test pulse for accuracy verification testing.
- Utility block and rolling average demand.
- Transformer Line Loss and CT/PT Compensation.
- Line frequency time sync.
- Sealable voltage and current inputs.
Measured Parameters | Accuracy% | Display Range |
---|---|---|
Voltage L-N | 0.1% | 0-9999 Scalable V or KV |
Voltage L-L | 0.2% | 0-9999 V or KV Scalable |
Current | 0.2% | 0-9999 A or KA |
+/- Watts | 0.2% | 0-9999 Watts, kWatts, MWatts |
+/-Wh | 0.2% | 5 to 8 Digits Programmable |
+/-VARs | 0.2% | 0-9999 VARs, KVARs, MVARs |
+/-VARh | 0.2% | 5 to 8 Digits Programmable |
VA | 0.2% | 0-9999 VA, KVA, MVA |
VAh | 0.2% | 5 to 8 Digits Programmable |
PF | 0.2% | +/- 0.5 to 1.0 |
Frequency | +/- 0.01 Hz | (45 to 65) Hz |
THD | +/- 2.0% | 1 to 99.99% |
Note: Applies to 3 element WYE and 2 element Delta connections. See full accuracy specifications in the ST40 Meter User Manual. Neutral current 2% accuracy. |

Extensive Data Logging Capability
(V2 and Above)
- Three independent historical trending logs of 64+ parameters each.
- Anti-tampering system events log records actions in the DIN rail energy meter.
- Power quality log provides timestamped magnitude and duration of up to 2048 events.
- Limit alarms log records out-of-limit events for up to eight programmed limits, including voltage and current unbalance.
Upgradable V-Switch™ Technology
- In-field upgrade of meter features.
- Begin with basic features and add more advanced capability when needed.
Features | V1 | V2 | V3 | V4 | V5 | V6 |
---|---|---|---|---|---|---|
Multifunction Measurement | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
Basic Data Logging | ✓ | ✓ | ✓ | |||
Intermediate Data Logging | ✓ | |||||
Advanced Data Logging | ✓ | |||||
Harmonic Analysis | ✓ | ✓ | ✓ | ✓ | ||
TLC and CT/PT Compensation | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
Limit Functions | ✓ | ✓ | ✓ | |||
64 Samples per Cycle Waveform Recorder | ✓ | |||||
512 Samples per Cycle Waveform Recorder | ✓ |